R-410A is not compatible with mineral oils because they are not properly mixed with them, the miner


Home News People and Figures Enterprises and Markets Technology and Advances From The Green Source Webcast New Product Air Conditioning Refrigeration Automation 3 tier buffet server Corporate Profile Articles Air Conditioning Refrigeration Automation Other Approaches 3 tier buffet server Editorial Letter Professional Edition Monthly Digital Webcast 3 tier buffet server TecnoEdificios Refriamericas Events Calendar Review Forums Air Conditioning Refrigeration Technology and Products General Concerns Other Services Webinars Register ARMACELL Subscription / Register Suppliers List Magazine Subscription Login
The refrigerant R-410A is a blend developed as the ultimate replacement for R-22 different original equipment applications. For new installations, a team with the right amount of charge and appropriate size pipe, R-410A has shown a (EER stands for Energy Efficiency Rating-Energy Efficiency Rating-) 5 to 6% higher the R-22.
It is a near azeotropic binary mixture of HFC-32 and HFC-125 which has a temperature glide of less than 0.2 C. See Table 1. Table 1 Components Properties Disadvantages 50% R-32 cold Flammable Good features, high working pressure 50% R-125 Reduces 3 tier buffet server Low flammability refrigerators, high performance greenhouse
Its properties are very similar to those of an azeotrope, so that it behaves as a single refrigerant, fractionation is very low, this means that it is not separated in the system and its composition does not change in case of a leak. Table: T C R-22 P saturation (psig) P saturation 410A (Psig) -1 55 99 7 76 129 43 225 363 54 295 473
Their superior thermodynamic properties can use more compact compressors, pipes of smaller diameter, higher speeds and make more efficient equipment because it has a lower energy loss.
R-410A is not compatible with mineral oils because they are not properly mixed with them, the mineral oil has the ability to dissolve uniformly in the coolant either in the liquid or vapor phase, resulting in a decrease index oil returning to the compressor, causing early failure.
The specified oil for R-410A are the polyols oils (POE), which being 15 times more hygroscopic than mineral oils, require to minimize their exposure to the environment.
The POE oils should never be stored in a way that exposed outdoors, 3 tier buffet server and should only be opened just before use. All systems must be closed until any replacement component is ready for installation.
When it is necessary to remove moisture absorbed by the POE oils, you must use a dryer filter in the liquid line and should ensure that the filter is compatible with R-410A. The moisture content of the POE should not exceed 100 ppm
The R-410A is not a direct replacement for R-22. The superior thermodynamic properties and high pressures make it difficult to use existing systems designed for R-22. In most cases the required changes that need to be performed in the system including the compressor, the VTE or capillary tube, condenser and in some cases, depending 3 tier buffet server on the applicable standard design for low pressure components, the evaporator. You also have to remove the mineral oil and replace it with a POE oil.
The compressor requires a device for relieving internal pressure of higher rank, between 600-650 psig, operating characteristics must take into account the higher suction pressures and discharge R-410A, and must use POE lubricant .
In the condenser 3 tier buffet server coil must be designed and tested to the high pressures of R-410A. The same applies to the breather filter, the filter requires a minimum pressure 3 tier buffet server rating of 600 psig operation, and only filters 3 tier buffet server approved for use of R-410A should be used.
The VTE also requires specific parameters and pressure variations that must go with the operating characteristics of R-410A. The VTE used with R-22 should not be used with R-410A. The capillary tubes must be modified to meet the operational requirements of the R-410A.
Pressure gauges must be specific to R-410A. You can not use conventional due to high pressure variations. Gauges, 3 tier buffet server hoses and variations of the indicators need to be high.
Standard work parameter hoses is 600 psig, which is not suitable for the R-410A refrigerant hoses for this parameter must have a work of 800 psig, and a breaking point of 4000 psig. This safety 3 tier buffet server margin of 5-1 is ne